2022 Cummins Power Generation Generator SET recalls and problems

The 2022 Cummins Power Generation Generator SET has 2 safety recalls. Recall repairs are free at any Cummins Power Generation dealer.

Recalls
2
Complaints
0
Crashes / fires
0 / 0
Injuries / deaths
0 / 0

Recalls may cover only some 2022 Cummins Power Generation Generator SET vehicles. Check your VIN at NHTSA ↗ to see open recalls for your exact car.

2022 Cummins Power Generation Generator SET recalls

Recall 24V-934: Equipment, Electrical System

Reported Dec 17, 2024 · 205 vehicles affected · Cummins, Inc.

Problem: Cummins, Inc. (Cummins) is recalling certain 2022-2024 Power Generation C275D2RE trailer-mounted generators. The unsecured wire leads may chafe against the starter motor housing or terminal and short circuit.

Risk: A short increases the risk of electrical shock or a fire.

Fix: Distributors or warranty repair locations will inspect and repair the generator set wiring harness and secure the wiring leads, free of charge. Owner notification letters were mailed February 7, 2025. Owners may contact Cummins customer service at 1-800-286-6467. Cummins' number for this recall is C5807.

Recall 22V-464: Equipment

Reported Jul 6, 2022 · 128 vehicles affected · Cummins, Inc.

Problem: Cummins, Inc. (Cummins) is recalling certain 2020-2022 Cummins Power Generation C500D6Re trailer-mounted generator sets (gensets). Incorrect logic in the output box door switch may cause the gensets to not shut down as intended when operated in parallel with other gensets.

Risk: The operator may be unaware that the gensets did not shut down, which could result in burns, electrical shock or arc flash, increasing the risk of injury.

Fix: Cummins will repair the electrical circuit, free of charge. Owner notification letters were mailed August 22, 2022. Owners may contact Cummins customer service at 1-800-286-6467.

Other Cummins Power Generation Generator SET years

Compare all Cummins Power Generation Generator SET years · All Cummins Power Generation models

Frequently asked questions

Does the 2022 Cummins Power Generation Generator SET have any recalls?

Yes — NHTSA lists 2 recalls for the 2022 Cummins Power Generation Generator SET: 24V-934 (equipment, electrical system), 22V-464 (equipment). Not every vehicle is affected, so check your VIN at nhtsa.gov/recalls.

Are Cummins Power Generation recall repairs free?

Yes. Safety recall repairs are free at authorized Cummins Power Generation dealers, whether you are the first owner or bought the car used.